PRODUCTHOME >> PRODUCT
Product information Back
- Product Name:FDM7-40, DPN
- Keyword:
- Be viewed: 2605 Times
Product introduction
Application It can protect the electric line equipment from overload and short circuit. Double safty for both neutral and line; Technical parameter ◆Standard: IEC 60898 ( EN60898) ◆Rated voltage: (Uc): 230V; 50/60 Hz ◆Rated breaking capacity: ◇6KA (2-20A) ◇4.5KA (25-40A) ◆DC breaking capacity: Max 50V/ single pole 6KA ◆Tripping curve: C curve ◆ The largest fuse can be connected: Max 100A gl ◆Selective level: III ◆Operating temperature: -5 + 40℃ ◆Protection class: IP40 ◆Electric life: ≥ 8000 times ◆Exposed length: 45mm ◆Casing height: 80 mm ◆Casing width: 17.5 mm ( 1P+N) ◆ Installation form: conform to IEC standard DIN rail 35mm ◆Terminal form: lifting terminals ◆Terminal connecting capacity: 1-10 mm2 Overall & installation dimensions Breaking Capacity: H: 10000A; N: 6000A; L: 4500A
|