Product introduction
FDR2
Application
FDR2 Series overload relays apply to circuit of AC 50Hz or 60Hz,rated voltage to below 660V and rated current 0.1A~93A for AC motor overload and open-phase protection during long time or intermittent long time service,which can also protect 3-phase serious imbalance and long starting time of motor or long time operation, can also be used for corresponding AC contactor for electromagnetic starter.
This product has innovative, elegant model and small installation area, functions such as temperature compensation,action indication,automatic and manual reset, stop with steady and reliable performance
Thermal relay can be combined/connected with contactor or installedseparately.
Standard: IEC 60947-4-1
 
Tripping curve
1. Equilibrium running, 3 phase, start from cold state
2. Equilibrium running, 2 phase, start from cold state
3. Equilibrium running, 3 phase, after long period of
setting current (hot state)
 
Technical Data
Type     FDR2-D13 FDR2-D23 FDR2-D33
Standard   A IEC60947-4-1 IEC60947-4-1 IEC60947-4-1
Rated working current Ie   V 25 36 96
Rated insulating voltage Ui     660 660 660
Phase failure protection function     yes yes yes
Automatic & manual reset     yes yes yes
Temperature compensation     yes yes yes
Releasing indicator     yes yes yes
Test & stop pushbutton     yes yes yes
Auxiliary contacts          
Rated current AC-15 230V A 2.73 2.73 2.73
AC-15 380V A 1.58 1.58 1.58
DC-13 230V A 0.2 0.2 0.2
Ambient air temperature.   -5 ~ +40 -5 ~ +40 -5 ~ +40
Altitude max   meter 2000 2000 2000
Pollution grade     3 3 3
Installation category     3 3 3
Mounting type Independent   yes yes yes
Plug-in   yes yes yes
 
Action Characteristics
Overload Protecion
Item No. Setting current multiple Action time Start condition Ambient air temperature
1 1.05 ≥ 2h Cold state start  
2 1.2 <2h After test item 1 20 ℃ ±5 ℃
3 1.5 <2min After test item 1  
4 7.2 2s Cold state start  
 
Phase failure protection
Item No. Setting current multiple Action time Start condition Ambient air temperature
Any two phase The third phase
5 1.0 0.9 ≥ 2h Cold state start 20°C±5°C
6 1.15 0 <2h After test item 5
 
Ref.

 
Model Setting Range(A) For Contactor Case Qty.(Pcs)
FDR2-25-D1301 0.10-0.16 FDC1-D09 100
FDR2-25-D1302 0.16-0.25 FDC1-D09 100
FDR2-25-D1303 0.25-0.40 FDC1-D09 100
FDR2-25-D1304 0.40-0.63 FDC1-D09 100
FDR2-25-D1305 0.63-1 FDC1-D09 100
FDR2-25-D1306 1-1.6 FDC1-D09 100
FDR2-25-D1307 1.6-2.5 FDC1-D09 100
FDR2-25-D1308 2.5-4 FDC1-D09 100
FDR2-25-D1310 4-6 FDC1-D09 100
FDR2-25-D1312 5.5-8 FDC1-D09 100
FDR2-25-D1314 7-10 FDC1-D12 100
FDR2-25-D1316 9-13 FDC1-D12 100
FDR2-25-D1321 12-18 FDC1-D18 100
FDR2-25-D1322 17-25 FDC1-D25 100
       
       
DR2-36-D2353 23-32 FDC1-D32 75
FDR2-36-D2355 30-40 FDC1-D32 75
       
       
FDR2-93-D3322 17-25 FDC1-D40 50
FDR2-93-D3353 23-32 FDC1-D40 50
FDR2-93-D3355 30-40 FDC1-D40 50
FDR2-93-D3357 37-50 FDC1-D50 50
FDR2-93-D3359 48-65 FDC1-D65 50
FDR2-93-D3361 55-70 FDC1-D80 50
FDR2-93-D3363 63-80 FDC1-D80 50
FDR2-93-D3365 80-93 FDC1-D95 50
 
Installation Dimensions (see Fig 1-Fig 3)
Operation Instruction (see Figure 4)
 
 
Matched relay Order code
FDR2-25 LA7-D1064
FDR2-36 LA7-D2064
FDR2-93 LA7-D3064
 
 
 