FDR1-F thermal overload relays are designed for use with contactors from FDC1-F115 to FDC1-F330. In addition to the protection provided by modular thermal overload relays FDR2, they offer the following special features:
|
□ Protection against phase imbalance.
|
□ Choice of starting class.
|
□ Protection of unbalanced circuits.
|
□ Protection of single-phase circuits.
|
|
Performance Curve
|
|
|
Specifications
|
Type
|
Number
|
Setting range(A)
|
For contactor
|
For contactor
|
F5357
|
30~50
|
FDC1-F115~F185
|
F5363
|
48~80
|
FDC1-F115~F185
|
F5367
|
60~100
|
FDC1-F115~F185
|
F5369
|
90~150
|
FDC1-F115~F185
|
F5371
|
132~220
|
FDC1-F225~F265
|
FDR1-F73
|
F7357
|
200~330
|
FDC1-F225~F500
|
F7379
|
300~500
|
FDC1-F225~F500
|
F7381
|
380~630
|
FDC1-F400~F630
|
|
|
Relay setting Order Code range
|
Fuses to be used with selected relay Maximum rating
|
Contactor
|
Order Code
|
aM Type gG Type
|
A
|
A
|
A
|
30-50
|
50
|
80
|
FDC1-F115…F185
|
FDR1-F5350
|
48-80
|
80
|
125
|
FDC1-F115…F185
|
FDR1-F5380
|
60-100
|
100
|
200
|
FDC1-F115…F185
|
FDR1-F53100
|
90-150
|
160
|
250
|
FDC1-F115…F185
|
FDR1-F53150
|
132-220
|
250
|
315
|
FDC1-F225…F265
|
FDR1-F53220
|
200-330
|
400
|
500
|
FDC1-F225…F500
|
FDR1-F53330
|
300-500
|
500
|
800
|
FDC1-F225…F500
|
FDR1-F53500
|
380-630
|
630
|
800
|
FDC1-F400…F630
|
FDR1-F53630
|
|