|   |  | FDR1-F thermal overload relays are designed for use with contactors from FDC1-F115 to FDC1-F330. In addition to the protection provided by modular thermal overload relays FDR2, they offer the following special features: | 
						
							| □ Protection against phase imbalance. | 
						
							| □ Choice of starting class. | 
						
							| □ Protection of unbalanced circuits. | 
						
							| □ Protection of single-phase circuits. | 
						
							|  | 
						
							| Performance Curve | 
						
							|   | 
						
							|  | 
						
							| Specifications | 
						
							| 
									
										
											| Type | Number | Setting range(A) | For contactor |  
											| For contactor | F5357 | 30~50 | FDC1-F115~F185 |  
											| F5363 | 48~80 | FDC1-F115~F185 |  
											| F5367 | 60~100 | FDC1-F115~F185 |  
											| F5369 | 90~150 | FDC1-F115~F185 |  
											| F5371 | 132~220 | FDC1-F225~F265 |  
											| FDR1-F73 | F7357 | 200~330 | FDC1-F225~F500 |  
											| F7379 | 300~500 | FDC1-F225~F500 |  
											| F7381 | 380~630 | FDC1-F400~F630 |  | 
						
							|  | 
						
							| 
									
										
											| Relay setting Order Code range | Fuses to be used with selected relay Maximum rating | Contactor | Order Code |  
											| aM Type gG Type |  
											| A | A | A |  
											| 30-50 | 50 | 80 | FDC1-F115…F185 | FDR1-F5350 |  
											| 48-80 | 80 | 125 | FDC1-F115…F185 | FDR1-F5380 |  
											| 60-100 | 100 | 200 | FDC1-F115…F185 | FDR1-F53100 |  
											| 90-150 | 160 | 250 | FDC1-F115…F185 | FDR1-F53150 |  
											| 132-220 | 250 | 315 | FDC1-F225…F265 | FDR1-F53220 |  
											| 200-330 | 400 | 500 | FDC1-F225…F500 | FDR1-F53330 |  
											| 300-500 | 500 | 800 | FDC1-F225…F500 | FDR1-F53500 |  
											| 380-630 | 630 | 800 | FDC1-F400…F630 | FDR1-F53630 |  |